TMV-Vd255W/N1-C1
2 TMV-Vd255W/N1-C1 EEV kits
The DC inverter motor with concentrated winding ensure higher efficiency.
Guarantees the reliability and energy saving of the refrigeration system.
Compressor efficiency
Large increase
0 20 40 60 80 100
Outdoor unit connects to wall mounted indoor units with EEV kits and Y branch -Method 3
One out door unit can connect 10 indoor units.
Branch Box TMV-V2P2BD/
N1DY(E)
TMV-V2P1BD/
N1DY(E)
TMV-V3P3BD/
N1DY(E)
TMV-V3P2BD/
N1DY(E)
TMV-V22-50G/
N1DY-B(E)
TMV-V56-80G/
N1DY-B(E)
Max. number of indoor unit 2 2 3 3 1 1
Appearance
Full DC Inverter Technology
By adopting full DC inverter technology to achieve 30% energy-saving compared with AC motor.
DC Inverter Compressor DC Inverter Fan Motor Self-developed VFD
DC Inverter Compressor
New Module
Normal Module
3
TMV-Vd255W/N1-C1
Highly integrated to achieve three drives on one board, improving system response speed and enhancing antiinterference ability .
No easily worn parts, high energy conversion, Shorter wiring, No external communication lines
TEC: TCL Electric Control
Self-developed TEC Control
Benefit
Other brand PCB
+ +
Filter board
Inverter board
Main board
TCL self-developed integrated PCB
Filter section
Inverter
section
Regrigerant
cooled
Main board section
The Mini VRF provides a total piping length possibility of 80m, a maximum height difference between
outdoor and indoor units of 30m. These generous allowances facilitate an extensive array of system designs.
L≤ 50m
(Between ODU and kit)
Level
difference
between
IDU-ODU
up(down) :30(20)m
Flexible Installation
6
Level
difference
between
IDU-ODU :8m
Communication wiring with ODU and IDU
Refrigerant piping between ODU and EEV kit
Refrigerant piping between IDU and EEV kit ,
EEV connection wiring
4 TMV-Vd255W/N1-C1 AI Energy saving Our system achieves an additional 20% energy
savings on top of full DC inverter technology.
This is accomplished via AI-driven adaptive
control with 0.1Hz precision for optimal lowpower efficiency.
Cooling steadily from -10 to 56 °C which meet various of working conditions and scenarios.
High VEEC Value
The Victorian Energy Upgrades (VEU) program
assists households and businesses to reduce
their energy bills and greenhouse gas emissions
by providing financial incentives to install
energy efficient equipment and appliances.
The VEEC value up to 106, higher than Midea
105, users can receive more subsidies from the
Australian government.
VEU Climatic Region Heating capacity(kW) Cooling capacity(kW) VEEC
Forupgrades in Metropolitan
25.5 21 106
Victoria-Climatic region mild
For upgrades in Regional
25.5 21 106
Victoria-Climatic region mild
Wide Operation Temperature Range -10°C ~ 56°C
-20 -10 0 10 20 30 40 50 60 70 °C
-10°C Cooling 56°C
-50 -40 -30 -20 -10 0 10 20 30 40 °C
-20°C Heating 28°C
5
TMV-Vd255W/N1-C1
Wide Voltage Range
Operation
4-stage Oil Return Technology
· Mini VRF ODU operation voltage range is from
198~264V, which is wider than standard.
· System can operate stably and reliable even in
unstable power supply area.
*Operation voltage range: 198-264V
4-stage oil control technology, ensure that compressor always has enough oil for lubrication to extend compressor
lifespan.
198V
264V
Level 1: Compressor internal oil separate.
Level 2: Compressor external oil separate.
Level 3: Automatic oil balance system improves the compressor reliability.
Level 4: High-efficiency centrifugal oil separator, oil return efficiency up to 99%.
Level 1
Oil /Mist separation
Oil block points
Centrifugal separation
Gravity separation
+
+
+
Oil return from the distributor
Level 1
Level 2
Level 3
Level 4
6 TMV-Vd255W/N1-C1 Dust Removing Design PreciseTemperature Control
Wide Angle Air Supply
Fan motor forward and reverse to remove dust
on fins keeps condenser fins good performance,
enhance stability.
*After self-clean mode , the outdoor fan will reverse automatically
According to the set temperature, the system will control the refrigerant flow precisely and adjust the evaporating/
condensing temperature automatically through the EEV and temperature sensor, which decrease the temperature
fluctuation to make sure the room temperature more confortable.
With up-down, left-right louver swing, cover more area to achieve mort comfort.
±0.5°C
TCL mini VRF Normal mini VRF
7
TMV-Vd255W/N1-C1
Intelligent Defrosting Technology
Noise Reduction
Intelligent defrosting technology ensure reduces defrosting time and provides user more comfortable.
The indoor units uses a low noise DC motor and external EEV design to reduce the noise generated during the
operation, the noise is as low as 22 dB(A), like the sound of leaves falling, to create a quiet and comfortable home
environment.
Ordinary Defrosting
Intelligent Defrosting
Heating Defrosting Temp. curve
DC motor
22dB(A)
+
8 TMV-Vd255W/N1-C1 Intelligent Control Lineup Overview
TCL Mini VRF After-sales Tool
Debugging Software
IDU
Wireless
Controller
58E
85T
52E 86J1 WIFI module 7-inch 3 in 1 gateway
(Cloud function)
IDU
Wired
Controller
WIFI
APP
Control
System
Centralized
Controller
System Cloud
Control and
Management
System BMS
Control
Voice controller
Built-in WIFI
10-inch
Protocol
Converter
Protocol
Converter
The third party
building control
systems
or smart home
systems
BMS gateway
Modbus/BACnet
86N3 T-smart APP New 7-inch TCL IOC
Platform
+
+
+
+ +
9
TMV-Vd255W/N1-C1
TCL Management System
High-end wired controller
Voice control, WIFI / OTA function, AI function, Group control, Constant air flow, ESP adjustment, Fresh air, Self-clean
Centralized control of indoor units and outdoor units
Estimate of energy consumption
Data Analysis
Schedule function
Monitor the detailed working statue of both indoor and
outdoor units
Running cost is calculated according to the running
time, refrigerant flow, etc.
Detail reports and bills of energy consumption are
available
Operating data records
Records and alarms for errors and faults
History of operating schedules
Annual, monthly and daily schedules are available
Schedules of individual or multiple units can be set,
which is convenient for centralized control
10 TMV-Vd255W/N1-C1 Centralized Controller TCL WiFi Control System
BMS Control System
High resolution display, Elegant & friendly Ul design, Individual, group control, Daily, weekly, holiday schedule
Data import & export, Energy consumption analysis
Monitoring and control of TCL's Mini VRF air conditioners can be integrated into building management systems,
enabling air conditioning to be monitored alongside lighting, elevator, fire, access and security systems. TCL's
gateway devices provide full compatibility with the leading BMS protocols: BACnet & Modbus.
Connect the device with APP by one click.
Remotely turn on/off and set schedule or
timer.Monitor running datas and operation
history.
10'' with 1280*800
resolution
Max.32 systems,
128 ODUs, 1024 IDUs
Note: 7’’ is under developing.
Max. 16 systems,
64 ODUs, 512 IDUs
7'' with 1440*720
resolution
TCL APP
WiFi module
Remote controller Wired controller
Third part BMS System
Lightning Fire alarm Elevator
Protocol Converter
(Modbus)
New 3 in 1 gateway
(Modbus + BACnet + Cloud) Protocol Converter
11
TMV-Vd255W/N1-C1
Maintenance
Branch kit installation
Using PC and RS485protocal converter connect with
ODU which could helps engineers monitor mini VRF
system operation datas quichkly , find the cause of
the malfunction and resolve the issue .
Choose a location that is convenient for installation.
Don’t install the EEV kit outside or rooftop in direct
sunlight
RS485
Protocal
Converter
PC
Debugging Software
Outdoor PCB has USB port to update new program
which convenient service engineers, Midea dosen’t
have this aftersales port .
Keep away from heat sources (such as smoke, open
flames) or harmful pollution below it.
Keep away from bedroom ,it’s better install inside the
corridor or washroom ceiling
12 TMV-Vd255W/N1-C1 1. Hoisting Installation Drawing of Branch Box (Unit: mm)
2. Wall-Mounted Installation Drawing of Branch Box (Unit: mm)
Installation
Installation Space
13
TMV-Vd255W/N1-C1
Orientation 1:
Leftward Connection √
Orientation 3:
Upward Connection ×
The connecting wires of the electronic expansion
valve shall be formed into a down ward U-bend
to ensure that the wiring hole of the branch box is
not the lowest point.
Orientation 2:
Rightward Connection √
Orientation 4:
Downward Connection √
The connecting wires of the electronic expansion
valve shall be formed into a downward U-bend to
ensure that the wiring hole of the branch box is
not the lowest point.
The connecting wires of the electronic expansion
valve shall be formed into a downward U-bend to
ensure that the wiring hole of the branch box is
not the lowest point.
Installation Direction for Wall-Mounted Instaliation
GD TCL INTELLIGENT HEATING & VENTILATING EQUIPMENT CO.,LTD.
Address: No.7 Yuanlin Road, Nantou, Zhongshan, Guangdong, PR China
Web : cac.tcl.com E-mail : hvac@tcl.com
TCL CAC TCL CAC TCL CAC HVAC-TCL TCL- CAC V26.04.02